Advanced Precision Transformer Insulation Analyzer for Tan Delta and Capacitance Testing |
Specifications: | ||
Accuracy: | Cx: | ±(read ×1%+1pF) |
tgδ: | ±(read ×1%+0.00040) | |
Anti interference: | Frequency conversion anti interference, under 200% interference, still can reach above accuracy. | |
Capacitance range: | Internal HV: | 3pF~60000pF/10kV/12kV 60pF~1μF/0.5kV |
External HV: | 3pF~1.5μF/10kV/12kV 60pF~30μF/0.5kV | |
External HV: | Max. 0.001pF, 4 significant figures | |
Tgδ range: | Unlimited,resolution: 0.001%,capacitance, inductance, resistance can be identified automatically. | |
Test current range: | 10μA~5A | |
Inner HV: | Setting voltage range: | 0.5~10kV/12kV |
Max. output current: | 200mA | |
Increase/decrease voltage: | Continuous slide regulating | |
Voltage precision: | ± (1.5%×reading+10V) | |
Voltage resolution: | 1V | |
Test frequency: | 45, 50, 55, 60, 65Hz single frequency | |
45/55Hz, 55/65Hz, 47.5/52.5Hz auto double frequency conversion | ||
Frequency precision: | ±0.01Hz | |
Outside HV: | UST Positive connection max. test current 1A,Power frequency or frequency conversion 40-70Hz | |
GST Negative connection max. test current: 10kV/1A,power frequency or frequency conversion 40-70Hz | ||
CVT self excitation LV output: | Output voltage 3~50V,output current 3~30A | |
Measuring duty: | About 40s, it depend on measuring methods | |
Input power supply: | 180V~270VAC,50Hz/60Hz±1%, local supply or by generator. | |
Build-in thermal printer | ||
Environmental Temperature: | -10ºC~50ºC | |
Relative humidity: | <90% |