| Customization: | Available |
|---|---|
| After-sales Service: | Onsite and Video Call Remote Guidance |
| Warranty: | 2 Years Free Warranty Long Life Service |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency

Test Range | Ratio -- 0.9 to 10000, Current -- 0 to 2000mA, Angle -- 0 to 360° | |
Ratio Accuracy | 5V Range ±(0.1% + 2 digits) (0.9-50), ±(0.2% + 2 digits) (51-200), ±(0.5% + 2 digits) (201-600); 80V Range ±(0.1% + 2 digits) (0.9-500), ±(0.2% + 2 digits) (501-2000), ±(0.5% + 2 digits) (2001-10000) | |
Current Accuracy | ±(1% of reading + 0.5 mA) | |
Angle Accuracy | ±0.2° | |
Output Voltage | Selectable 5V or 80V | |
Resolution | Ratio -- Minimum 0.0001, Current -- 0.001mA, Angle -- 0.01° | |
Test Voltage | AC 5V @ 1A, AC 80V @ 80mA | |
Operating Power Supply | 220V AC, 50/60 Hz | |
Ambient Temperature | -10°C to 40°C | |
Relative Humidity | ≤85%, non-condensing | |